physics : class12 Inductive Power Factor : Inductive Reactance : Electromagnetic Induction and Alternating Currents MCQ Questions and Answers
Practice important
Inductive Power Factor
MCQ questions and answers.
Page 1
of
1
|
10
MCQ Questions
1. An inductive AC circuit has resistance 24 Ω and inductive reactance 18 Ω. What is its power factor?
A.
0.60 lagging
B.
0.75 lagging
C.
0.80 lagging
D.
0.90 lagging
Correct Answer:
0.80 lagging
Explanation:
For a series inductive circuit, power factor = R/Z, where Z = √(R² + X_L²) = √(24² + 18²) = 30 Ω. Thus, power factor = 24/30 = 0.80, and it is lagging because the circuit is inductive.
2. An inductive load consumes 3.6 kW of real power from an AC supply and has an apparent power of 4.5 kVA. What is its reactive power?
A.
1.8 kVAR leading
B.
2.1 kVAR lagging
C.
2.7 kVAR lagging
D.
3.6 kVAR lagging
Correct Answer:
2.7 kVAR lagging
Explanation:
The power factor is P/S = 3.6/4.5 = 0.8, so sin φ = 0.6. Therefore, reactive power Q = S sin φ = 4.5 × 0.6 = 2.7 kVAR. It is lagging for an inductive load.
3. A 230 V RMS supply feeds an inductive load drawing 5 A RMS. If the average power consumed is 920 W, what is the power factor?
A.
0.60 lagging
B.
0.80 lagging
C.
0.92 lagging
D.
1.00
Correct Answer:
0.80 lagging
Explanation:
The apparent power is S = VI = 230 × 5 = 1150 VA. Hence, power factor = P/S = 920/1150 = 0.80. Since the load is inductive, the power factor is lagging.
4. Two inductive loads connected in parallel consume real powers of 2.0 kW and 1.5 kW, with reactive powers of 1.5 kVAR and 2.0 kVAR, respectively. What is the combined power factor?
A.
0.600 lagging
B.
0.707 lagging
C.
0.800 lagging
D.
0.875 lagging
Correct Answer:
0.707 lagging
Explanation:
Total real power is 3.5 kW and total reactive power is 3.5 kVAR. Therefore, the apparent power is √(3.5² + 3.5²) = 4.95 kVA. The power factor is 3.5/4.95 ≈ 0.707, lagging because the net reactive power is inductive.
5. The power factor of an inductive load is 0.6 lagging. What is the phase angle by which the current lags the voltage?
A.
36.87°
B.
45.00°
C.
53.13°
D.
66.42°
Correct Answer:
53.13°
Explanation:
Power factor = cos φ = 0.6. Therefore, φ = cos⁻¹(0.6) = 53.13°. For an inductive load, current lags voltage by this angle.
6. An inductive impedance has magnitude 20 Ω and power factor 0.6 lagging. What are the resistance and inductive reactance of the impedance?
A.
R = 12 Ω, X_L = 16 Ω
B.
R = 16 Ω, X_L = 12 Ω
C.
R = 10 Ω, X_L = 17.32 Ω
D.
R = 8 Ω, X_L = 18.33 Ω
Correct Answer:
R = 12 Ω, X_L = 16 Ω
Explanation:
For an inductive impedance, power factor = R/Z. Thus, R = 0.6 × 20 = 12 Ω. The inductive reactance is X_L = √(Z² − R²) = √(400 − 144) = 16 Ω.
7. An inductive load operates at constant voltage and consumes constant real power. Its power factor changes from 0.8 lagging to 0.6 lagging. By what factor does the supply current change?
A.
It becomes 0.75 times its original value
B.
It becomes 1.25 times its original value
C.
It becomes 1.33 times its original value
D.
It becomes 1.60 times its original value
Correct Answer:
It becomes 1.33 times its original value
Explanation:
For constant real power and voltage, I = P/(V cos φ), so current is inversely proportional to power factor. Therefore, I₂/I₁ = 0.8/0.6 = 4/3 ≈ 1.33.
8. An inductive load draws 10 A from a 400 V RMS supply and has a wattmeter reading of 2.4 kW. What is its power factor?
A.
0.40 lagging
B.
0.50 lagging
C.
0.60 lagging
D.
0.75 lagging
Correct Answer:
0.60 lagging
Explanation:
The apparent power is S = VI = 400 × 10 = 4000 VA. Thus, power factor = P/S = 2400/4000 = 0.60. The factor is lagging because the load is inductive.
9. For an inductive circuit, the current is represented by I = I₀ sin(ωt − φ), while the voltage is V = V₀ sin(ωt). If the power factor is 0.8 lagging, which statement is correct?
A.
φ = 36.87° and the average power is 0.8 V_rms I_rms
B.
φ = 53.13° and the average power is 0.8 V_rms I_rms
C.
φ = 36.87° and the average power is 0.6 V_rms I_rms
D.
φ = 53.13° and the average power is 0.6 V_rms I_rms
Correct Answer:
φ = 36.87° and the average power is 0.8 V_rms I_rms
Explanation:
A power factor of 0.8 gives φ = cos⁻¹(0.8) = 36.87°. The average power is P = V_rms I_rms cos φ = 0.8 V_rms I_rms. The negative phase term confirms that current lags voltage.
10. A series inductive circuit has resistance 8 Ω. When its inductive reactance is 6 Ω, its power factor is 0.8. If the inductive reactance increases to 10 Ω while resistance remains unchanged, what is the new power factor?
A.
0.500 lagging
B.
0.625 lagging
C.
0.750 lagging
D.
0.800 lagging
Correct Answer:
0.625 lagging
Explanation:
With X_L = 10 Ω, the impedance is Z = √(8² + 10²) = √164 ≈ 12.81 Ω. Hence, the new power factor is R/Z = 8/12.81 ≈ 0.625, lagging. Increasing inductive reactance lowers the power factor.